Engineering ToolBox - Resources, Tools and Basic Information for Engineering and Design of Technical Applications!

This is an AMP page - Open full page! for all features.

Search is the most efficient way to navigate the Engineering ToolBox!

Standard State and Enthalpy of Formation, Gibbs Free Energy of Formation, Entropy and Heat Capacity

Sponsored Links

The term standard state is used to describe a reference state for substances, and is a help in thermodynamical calculations (as enthalpy, entropy and Gibbs free energy calculations). The superscript degree symbol (°) indicates that substances are in their standard states. (ΔH°, ΔG°, S°.....)

Definitions of standard states:

  • For a gas, the standard state is as a pure gaseous substance as a (hypothetical) ideal gas at a pressure of exactly 1 bar.
  • For a substance present in a solution, the standard state is a concentration of exactly 1 M at an applied pressure of 1 bar, but exhibiting infinite-dilution behavior. (Hence taking infinite-dilution behavior to be the standard state allows corrections for non-ideality to be made consistently for all the different solutes.)
  • For a pure substance in a condensed state (liquid or solid), the standard state is the pure liquid or solid under 1 bar pressure.
  • For an element the standard state is the form in which the element exists (is more stable) under condition of 1 bar and at the temperature of interest (usually 25°C).
    • ΔH0f for an element in its standard state is zero. Thus, elements in their standard states are not included in the ΔHreaction calculations.

Note! Standard state is NOT the same as standard temperature and pressure (STP) for a gas, and must not be confused with this term.

Enthalpy is a state function, defined by the internal energy (E), the pressure (P) and volume (V) of a system:

H = E + PV  and  ΔH = ΔE + Δ(PV)

For enthalpy, there are no method to determine absolute values, only enthalpy changes (ΔH values) can be measured. Then it is important to have a common and  well defined reference state. Since enthalpy is a state function, a change in enthalpy does not depend on the pathway between two states.

Hess's law: In going from a particular set of reactants to a particular set of products, the change in enthalpy is the same whether the reaction takes place in one step or in a series of steps.

At constant pressure:    ΔH  = q   (qp = heat from or to the chemical system at constant pressure,  q is also called heat of reaction)

Exothermic reaction:     negative ΔH    (heat transferred to the surroundings from the system)

Endothermic reaction:  positive  ΔH    (heat adsorbed by the system from the surroundings)

The standard enthalpy of formation (ΔH0f) of a compound is the change in enthalpy that accompanies the formation of 1 mole of a compound from its elements with all substances in their standard states.

.


The table below  shows the standard enthalpy of formation, the standard Gibbs free energy of formation, standard entropy and molar heat capacity at constant pressure of several inorganic compounds.

See also Standard enthalpy of formation, Gibbs free energy of formation, entropy and molar heat capacity of organic substances  and Thermodyamics key values internationally agreed for tabulation of more of the same type of values

Substances - Standard State and Enthalpies of Formation, Gibbs Free Energies of Formation, Entropies and Heat Capacities
SubstanceΔH0f @25°C
(kJ/mol)
ΔG0f @25°C
(kJ/mol)
S0 @25°C
(J/(molK))
Cp @25°C
J/(mol K)
Ag(g) 284.9 246 173 20.8
Ag(s) 0 0 42.6 25.4
Ag+(aq) 105.8 77.1 73.5
AgCN(s) 146 156.9 107.2 66.7
Ag2CO3(s) -505.8 -436.8 167.4 112.3
AgNO3(s) -124.4 -33.4 140.9 93.1
Ag2O(s) -31.1 -11.2 121.3 65.9
Ag2S(s) -32.6 -40.7 144 76.5
AgBr(s) -100.4 -96.9 107.1 52.4
AgCl(s) -127.0 -109.8 96.3 50.8
AgF(s) -204.6 -187 84
AgI(s) -61.8 -66.2 115.5 56.8
Al(g) 330 289.4 164.6 21.4
Al(s) 0 0 28.3 24.2
Al2O3(s) -1675.7 -1582.3 50.9 79.0
AlF3(s) -1510.4 -1431.1 66.5 75.1
AlI3(s) -302.9 195.9
AlBr3(s) -527.2 180.2 100.6
AlCl3(s) -704.5 -628.11 112.3 91.1
Al(OH)3(s) -1277
Al(OH)4-(aq) -1490 -1297 117
AlPO4(s) -1733.8 -1617.9 90.8 93.2
Ar(g) 0 154.9 20.8
B(s) 0 0 5.9 11.1
B(g) 565 521.0 153.4 20.8
BH(g) 442.7 412.7 171.8 29.2
BH3(g) 89.2 93.3 188.2 36.0
B2S3(s) -240.6 100.0 111.7
Ba(g) 180 146 170.2
Ba(s) 0 0 62.5 28.1
BaCO3(s) -1213.0 -1134.4 112.1 86.0
BaH2(s) -177 -138.2 63.0
BaBr2(s) -757.3 -736.8 146.0
BaCl2(s) -855 -806.7 123.7 75.1
BaF2(s) -1207.1 -1156.8 96.4 71.2
BaI2(s) -602.1 -597 167.0
BaO(s) -548.0 -520.3 72.1 47.3
BaSO4(s) -1473.2 -1362.2 132.2 101.8
Be(g) 324 286.6 136.3 20.8
Be(s) 0 0 9.5 13.4
BeBr2(s) -353.5 108 69.4
BeCl2(s) -490.4 -445.6 75.8 62.4
BeF2(s) -1026.8 -979.4 53.4 51.8
BeI2(s) -192.5 121 71.1
BeO(s) -609.4 -580.1 13.8 25.6
Be(OH)2(s) -902.5 -815.0 45.5 62.1
BeSO4(s) -1205.2 -1093.8 77.9 85.7
Bi(g) 207.1 168.2 187 20.8
Bi(s) 0 0 56.7 25.5
Bi2O3(s) -573.9 -493.7 151.5 113.5
BiCl3(s) -379.1 -315.0 177.0 105.0
Br-(aq) -121.4 -104.0 82.6
Br(g) 111.9 82.4 175 20.8
Br2(g) 30.9 3.1 245.5 36.0
Br2(l) 0 0 152.2 75.7
BrCl(g) 14.6 -1 240.1 35.0
BrF(g) -93.8 -109.2 229 33.0
BrF3(g) -1136 1119.4 254.4 66.6
C(g) 716.7 671.3 158.1 0.8
C(s, diamond) 1.9 2.9 2.4 6.1
C(s, graphite) 0 0 5.7 8.5
CBr4(g) 83.9 67 358.1
CBr4(s) 29.4 47.7 212.5
CCl2F2(g) -477.4 -439.4 300.8
CCl2O(g) -219.1 -204.9 283.5
CCl4(g) -95.7 -53.6 309.9
CCl4(l) -128.2 -62.6 216.2
CF4(g) -933.6 -888.3 261.6
CS2(g) 116.7 67.1 237.8 45.4
CS2(l) 89 64.6 151.3 76.4
CO(g) -110.5 -137.2 197.7 29.1
CO2(g) -393.5 -394.4 213.8 37.1
Ca(g) 177.8 144 154.9 20.8
Ca(s) 0 0 41.6 25.9
Ca(OH)2(s) -985.2 -897.5 83.4 87.5
CaBr2(s) -682.8 -663.6 130
CaCl2(s) -795.4 -748.8 108.4 72.9
CaCN(s) -184.5
CaCO3(s, aragonite) -1207.8 -1128.2 88 82.3
CaCO3(s, calcite) -1207.6 -1129.1 91.7 83.5
CaF2(s) -1228.0 -1175.6 68.5 67.0
CaH2(s) -181.5 -142.5 41.4 41.0
CaI2(s) -533.5 -528.9 142
CaO(s) -634.9 -603.3 38.1 42.0
CaSO4(s) -1434.5 -1322.0 106.5 99.7
Cd(g) 111.8 167.7 20.8
Cd(s) 0 0 51.8 26.0
CdBr2(s) -316.2 -296.3 137.2 76.7
CdCl2(s) -391.5 -343.9 115.3 74.7
CdCO3(s) -750.6 -669.4 92.5
CdF2(s) -700.4 -647.7 77.4
CdS(s) -161.9 -156.5 64.9
CdSO4(s) -933.3 -822.7 123.0 99.6
Cl-(aq) -167.1 -131.2 56.6
Cl(g) 121.3 105.3 165.2 21.8
Cl2(g) 0 0 223.1 33.9
ClF(g) -50.3 -51.8 217.9 32.1
ClF3(g) -163.2 -123.0 281.6 63.9
ClO2(g) 89.1 105 263.7 46.0
Cl2O(g) 80.3 97.9 266.2 45.4
Co(g) 424.7 380.3 179.5 23.0
Co(s) 0 0 30 24.8
CoCl2(s) -312.5 -269.8 109.2 78.5
Cr(g) 396.6 351.8 174.5 20.8
Cr(s) 0 0 23.8 23.4
Cr2O3(s) -1139.7 -1058.1 81.2 118.7
CrCl2(s) -395.4 -356 115.3 71.2
CrCl3(s) -556.5 -486.1 123 91.8
CrO2(g) -598
CrO3(g) -292.9 266.2 56.0
Cs(g) 76.5 49.6 175.6 20.8
Cs(s) 0 0 85.2 32.2
CsCl(s) -443.0 -414.5 101.2 52.5
Cu(g) 337.4 297.7 166.4 20.8
Cu(s) 0 0 33.2 24.2
Cu2O(s) -168.6 -146.0 93.1 63.6
CuO(s) -157.3 -129.7 42.6
Cu2S(s) -79.5 -86.2 120.9 76.3
CuS(s) -53.1 -53.6 66.5 47.8
CuSO4(s) -771.4 -662.2 109.2
CuBr(s) -104.6 -100.8 96.1 54.7
CuBr2(s) -141.8
CuCl(s) -137.2 -119.9 86.2 48.5
CuCl2(s) -220.1 -175.7 108.1 71.9
CuCN(s) 96.2 111.3 84.5
F-(aq) -335.4 -278.8 -13.8
F(g) 79.4 62.3 158.8 22.7
F2(g) 0 0 202.8 32.3
F2O(g) 24.5 41.8 247.5 43.3
FO(g) 109 105.3 216.4 32.0
FB(g) -122.2 -149.8 200.5 58.6
Fe(g) 416.3 370.7 180.5 25.7
Fe(s) 0 0 27.3 25.1
FeO(s) -272.0 -251.4 60.7
Fe2+(aq) -89.1 -78.9 -137.7
Fe2O3(s) -824.2 -742.2 87.4 103.9
Fe3+(aq) -48.5 -4.7 -315.9
Fe3O4(s) -1118.4 -1015.4 146.4 143.4
FeCO3(s) -740.6 -666.7 92.9 82.1
FeS2(s) -178.2 -166.9 52.9 62.2
FeCl2(s) -341.8 -302.3 118 75.7
FeCl3(s) -399.5 -334.0 142.3 96.7
FeBr2(s) -249.8 -238.1 140.6
FeBr3(s) -268.2
Fe3C(s) 25.1 20.1 104.6 105.9
H(g) 218.0 203.3 114.7 20.8
H+(aq) 0 0 0
H2(g) 0 0 130.7 28.8
H2O(g) -241.8 -228.6 188.8 33.6
H2O(l) -285.8 -237.1 70.0 75.3
H2O2(g) -136.3 -105.6 232.7 43.1
H2O2(l) -187.8 -120.4 109.6 89.1
H2S(g) -20.6 -33.4 205.8 34.2
H2Se(g) 29.7 15.9 219 34.7
H2SO4(aq) -909.3 -744.5 20.1
H2SO4(l) -814.0 -690.0 156.9 138.9
H3PO4(l) -1271.7 -1123.6 150.8 145.0
H3PO4(s) -1284.4 -1124.3 110.5 106.1
HBr(aq) -121.6 -104.0 82.4
HBr(g) -36.3 -53.4 198.7 29.1
HCl(aq) -167.2 -131.2 56.5
HCl(g) -92.3 -95.3 186.9 29.1
HCN(g) 135.1 124.7 201.8 35.9
HCN(l) 108.9 125 112.8 70.6
HF(aq) -332.6 -278.8 -13.8
HF(g) -273.3 -275.4 173.8
HI(aq) -55.2 -51.6 111.3
HI(g) 26.5 1.7 206.6 29.2
HNO2(g) -79.5 -46.0 254.1
HNO3(aq) -207.4 -111.3 146.4
HNO3(g) -133.9 -73.5 266.9 54.1
HNO3(l) -174.1 -80.7 155.6 109.9
He(g) 0 0 126.2 20.8
Hg(g) 61.4 31.8 175
Hg(l) 0 0 75.9 28.0
Hg2(g) 108.8 68.2 288.1
HgO(s) -90.8 -58.5 70.3 44.1
HgS(s, red) -58.2 -50.6 82.4 48.4
Hg2SO4(s) -743.1 -625.8 200.7 132.0
HgSO4(s) -707.5
Hg2Cl2(s) -265.4 -210.7 191.6 191.6
HgCl2(s) -224.3 -178.6 146.0 146.0
Hg2Br2(s) -206.9 -181.1 218.0 218.0
HgBr2(s) -170.7 -153.1 172.0 172.0
Hg2I2(s) -121.3 -111 233.5 233.5
HgI2(s) -105.4 -101.7 180.0 180.0
I-(aq) -56.8 -51.6 106.5
I(g) 106.8 70.2 180.8 20.8
I2(g) 62.4 19.3 260.7 36.9
I2(s) 0 0 116.1 54.4
HIO3(s) -230.1
IBr(g) 40.8 3.7 258.8 36.4
ICl(g) 17.8 -5.5 247.6 35.6
IF(g) -95.7 -118.5 236.2 33.4
K(g) 89.0 60.5 160.3 20.8
K(s) 0 0 64.7 29.6
K2CO3(s) -1151.0 -1063.5 155.5 114.4
K2O(s) -361.5 -322.1 94.1
K2O2(s) -494.1 -425.1 102.1
K2SO4(s) -1437.8 -1321.4 175.6 131.5
KBr(s) -393.8 -380.7 95.9 52.3
KCl(s) -436.5 -408.5 82.6 51.3
KF(s) -567.3 -537.8 66.6 49.0
KI(s) -327.9 -324.9 106.3 52.9
KClO3(s) -397.7 -296.3 143.1 100.3
KMnO4(s) -837.2 -737.6 171.7 117.6
KNO2(s) -369.8 -306.6 152.1 107.4
KNO3(s) -494.6 -394.9 133.1 96.4
KSCN(s) -200.2 -178.3 124.3 88.5
Kr(g) 0 0 164.1 20.8
Li(g) 159.3 126.6 138.8 20.8
Li(s) 0 0 29.1 24.9
Li+(aq) -278.5 -293.3 12.4
Li2O(s) -597.9 -561.2 37.6 54.1
LiOH(s) -487.5 -441.5 42.8 49.6
LiNO3(s) -483.1 -381.1 90.0
LiBr(s) -351.2 -342 74.3
LiCl(s) -408.6 -384.4 59.3 48.0
LiF(s) -616 -587.7 35.7 41.6
LiI(s) -270.4 -270.3 86.8 51.0
Mg(g) 147.1 112.5 148.6 20.8
Mg(s) 0 0 32.7 24.9
MgO(s) -601.6 -569.3 27.0 37.2
Mg(OH)2(s) -924.5 -833.5 63.2 77.0
MgS(s) -346.0 -341.8 50.3 45.6
MgSO4(s) -1284.9 -1170.6 91.6 96.5
MgBr2(s) -524.3 -503.8 117.2
MgCl2(s) -641.3 -591.8 89.6 71.4
MgF2(s) -1124.2 -1071.1 57.2 61.6
Mn(g) 280.7 238.5 173.7 20.8
Mn(s) 0 0 32 26.3
MnO(s) -385.2 -362.9 59.7 45.4
MnO2(s) -520.0 -465.1 53.1 54.1
MnO4-(aq) -541.4 -447.2 191.2
MnBr2(s) -384.9
MnCl2(s) -481.3 -440.5 118.2 72.9
Mo(g) 658.1 612.5 182 20.8
Mo(s) 0 0 28.7 24.1
MoO2(s) -588.9 -533.0 46.3 56.0
MoO3(s) -745.1 -668.0 77.7 75.0
MoS2(s) -235.1 -225.9 62.6 63.6
MoS3(s) -364 -354 119
N(g) 472.7 455.5 153.3 20.8
N2(g) 0 0 191.6 29.1
NF3(g) -132.1 -90.6 260.8 53.4
NH3(g) -45.9 -16.4 192.8 35.1
NH4+(aq) -133.3 -79.3 111.2
NH4Cl(s) -314.4 -202.9 94.6 84.1
NH4NO3(s) -365.6 -183.9 151.1 139.3
NH4OH(l) -361.2 -254.0 165.6 154.9
(NH4)2SO4(s) -1180.9 -901.7 220.1 187.5
N2H4(g) 95.4 159.4 238.5
N2H4(l) 50.6 149.3 121.2
NO2(g) 33.2 51.3 240.1 37.2
N2O(g) 81.6 103.7 220 38.6
NO(g) 91.3 87.6 210.8
N2O4(g) 11.1 99.8 304.4 79.2
N2O4(l) -19.5 97.5 209.2 142.7
Na(g) 107.5 77 153.7 20.8
Na(s) 0 0 51.3 28.2
Na+(aq) -240.2 -261.9 58.5
Na2CO3(s) -1130.7 -1044.4 135 112.3
Na2O(s) -414.2 -375.5 75.1 69.1
Na2O2(s) -510.9 -447.7 95 89.2
Na2SO4(s) -1387.1 -1270.2 149.6 128.2
NaBr(aq) -361.7 -365.8 141.4
NaBr(g) -143.1 -177.1 241.2 36.3
NaBr(s) -361.1 -349.0 86.8 51.4
NaCl(aq) -407.3 -393.1 115.5
NaCl(s) -411.2 -384.1 72.1 50.5
NaCN(s) -87.5 -76.4 115.6 70.4
NaF(aq) -572.8 -540.7 45.2
NaF(s) -576.6 -546.3 51.1 46.9
NaN3(s) 21.7 93.8 96.9 76.6
NaNO3(aq) -447.5 -373.2 205.4
NaNO3(s) -467.9 -367.0 116.5 92.9
NaO2(s) -260.2 -218.4 115.9 72.1
NaOH(s) -425.8 -379.7 64.4 59.5
NaH(s) -56.3 -33.6 40 36.4
Ne(g) 0 0 146.3 20.8
Ni(g) 429.7 384.5 182.2 23.4
Ni(s) 0 0 29.9 26.1
Ni2O3(s) -489.5
Ni(OH)2(s) -529.7 -447.2 88
NiBr2(s) -212.1
NiCl2(s) -305.3 -259.0 97.7 71.7
NiF2(s) -651.4 -604.1 73.6 64.1
O(g) 249.2 231.7 161.1 21.9
O2(g) 0 0 205.2 29.4
O3(g) 142.7 163.2 238.9 39.2
OH-(aq) -230.0 -157.2 -10.9
Os(g) 791 745 192.6 20.8
Os(s) 0 0 32.6 24.7
OsO4(g) -337.2 -292.8 293.8 74.1
OsO4(s) -394.1 -304.9 143.9
P(g, white) 316.5 280.1 163.2 20.8
P(s, black) -39.3
P(s, red) -17.6 -12.5 22.8 21.2
P(s, white) 0 0 41.1 23.8
P2(g) 144.0 103.5 218.1
P4(g) 58.9 24.4 280.0
PCl3(g) -287.0 -267.8 311.8 71.8
PCl3(l) -319.7 -272.3 217.1
PCl5(g) -374.9 -305.0 364.6 112.8
PH3(g) 5.4 13.5 210.2 37.1
POCl3(g) -558.5 -512.9 325.5
POCl3(l) -597.1 -520.8 222.5
Pb(g) 195.2 162.2 175.4 20.8
Pb(s) 0 0 64.8 26.8
PbCl2(s) -359.4 -314.1 136
PbCO3(s) -699.1 -625.5 131 87.4
PbO(s, red or litharge) -219.0 -188.9 66.5 45.8
PbO(s, yellow or massicot) -217.3 -187.9 68.7 45.8
PbO2(s) -277.4 -217.3 68.6 64.6
Pb(NO3)2(aq) -416.3 -246.9 303.3
Pb(NO3)2(s) -451.9
PbS(s) -100.4 -98.7 91.2 49.5
PbSO4(s) -920.0 -813.0 148.5 103.2
Rb(g) 80.9 53.1 170.1 20.8
Rb(s) 0 0 76.8

31.1

RbCl(s) -435.4 -407.8 95.9 52.4
S(g, rhombic) 277.2 236.7 167.8 23.7
S(s, rhombic) 0 0 32.1 22.6
SO2(g) -296.8 -300.1 248.2 39.9
SO3(g) -395.7 -371.1 256.8 50.7
SO42-(aq) -909.3 -744.5 18.5
SOCl2(g) -212.5 -198.3 309.8
Se(g, gray) 227.1 187 176.7
Se(s, gray) 0 0 42.4 25.4
Si(g) 450 405.5 168.0 22.3
Si(s) 0 0 18.8 20.0
SiC(s, cubic) -65.3 -62.8 16.6 26.9
SiC(s, hexagonal) -62.8 -60.2 16.5 26.7
SiCl4(g) -657.0 -617.0 330.7
SiCl4(l) -687.0 -619.8 239.7
SiH4(g) 34.3 56.9 204.6 42.8
Sn(g, white) 301 266.2 168.5 21.3
Sn(s, gray) -2.1 0.1 44.1 25.8
Sn(s, white) 0 0 51.2 27.0
SnCl4(g) -471.5 -432.2 365.8 98.3
SnCl4(l) -511.3 -440.1 258.6 165.3
SnO2(s) -557.6 -515.8 49 52.6
Ti(g) 473 428.4 180.3 24.4
Ti(s) 0 0 30.7 25.1
TiCl2(s) -513.8 -464.4 87.4 69.8
TiCl3(s) -720.9 -653.5 139.7 97.2
TiCl4(g) -763 -726.3 353 95.4
TiCl4(l) -804.2 -737.2 252.3 145.2
TiO2(s) -944.0 -888.8 50.6 55.0
U(g) 533 488.4 199.8 23.7
U(s) 0 0 50.2 27.7
UF4(g) -1598.7 -1572.7 368 91.2
UF4(s) -1914.2 -1823.3 151.7 116.0
UF6(g) -2147.4 -2063.7 377.9 129.6
UF6(s) -2197.0 -2068.5 227.6 166.8
UO2(g) -465.7 -471.5 274.6 51.4
UO2(s) -1085.0 -1031.8 77.0 63.6
V(g) 514.2 754.4 182.3 26.0
V(s) 0 0 28.9 24.9
V2O5(s) -1550.6 -1419.5 131.0 127.7
VCl3(s) -580.7 -511.2 131.0 93.2
VCl4(g) -525.5 -492.0 362.4 96.2
VCl4(l) -569.4 -503.7 255.0
Xe(g) 0 0 169.7 20.8
Zn(g) 130.4 94.8 161.0 20.8
Zn(s) 0 0 41.6 25.4
ZnBr2(s) -328.7 -312.1 138.5
ZnCl2(s) -415.1 -369.4 111.5 71.3
ZnF2(s) -764.4 -713.3 73.7 65.7
ZnI2(s) -208.0 -209.0 161.1
Zn(NO3)2(s) -483.7
ZnS(s, sphalerite) -206.0 -201.3 57.7 46.0
ZnSO4(s) -982.8 -871.5 110.5 99.2
Zr(g) 608.8 566.5 181.4 26.7
Zr(s) 0 0 39 25.4
ZrCl2(s) -502.0 -386 110
ZrCl4(s) -980.5 -889.9 181.6 119.8

For conversion of units, use the Specific heat online unit converter.

See also tabulated values of specific heat capacity of gases, food and foodstuffmetals and semimetals, common liquids and fluidscommon solids, and other common substances as well as values of molar heat capacity of  common organic substances.

The specific heat capacity can be calculated from the molar heat capacity, and vise versa:

cp = Cp/ M    and  

Cp = cp . M

where

cp = specific heat capacity

Cp = molar heat capacity

M = molar weight of the actual substance (g/mol).

Sponsored Links

Related Topics

Basics

Basic engineering data. SI-system, unit converters, physical constants, drawing scales and more.

Material Properties

Properties of gases, fluids and solids. Densities, specific heats, viscosities and more.

Thermodynamics

Work, heat and energy systems.

Related Documents

1st Law of Thermodynamics

The First Law of Thermodynamics simply states that energy can be neither created nor destroyed (conservation of energy). Thus power generation processes and energy sources actually involve conversion of energy from one form to another, rather than creation of energy from nothing.

2nd Law of Thermodynamics

Entropy and disorder.

Acetone - Thermophysical Properties

Chemical, physical and thermal properties of acetone, also called 2-propanone, dimethyl ketone and pyroacetic acid. Phase diagram included.

Benzene - Thermophysical properties

Chemical, physical and thermal properties of benzene, also called benzol. Phase diagram included.

Combustion Heat

Heat of combustion (energy content) for som common substances - with examples how to calculate heat of combustion.

Ethylene - Thermophysical Properties

Chemical, physical and thermal properties of ethylene, also called ethene, acetene and olefiant gas. Phase diagram included.

Heat Capacity

The amount of heat required to change the temperature of a substance by one degree.

Heat, Work and Energy

Heat vs. work vs. energy.

Inorganic Compounds in Water - Melting and Boiling Temperature, Density and Solubility

Physical constants for more than 280 common inorganic compounds. Density is given for the actual state at 25°C and for liquid phase at melting point temperature.

Metals - Specific Heats

Specific heat of commonly used metals like aluminum, iron, mercury and many more - imperial and SI units.

Standard enthalpy of formation, Gibbs energy of formation, entropy and molar heat capacity of organic substances

The standard enthalpy of formation, Gibbs energy of formation, entropy and molar heat capacity are tabulated for more than hundred organic substances.

Standardized Enthalpies and Entropies

Standardized enthalpies and entropies for some common substances.

Superheated Steam - Enthalpy

Enthalpy of steam superheated to temperatures above it's boiling point.

Thermodynamic Key Values Internationally Agreed

Internationally agreed, internally consistent, values for the thermodynamic properties (standard enthalpy of formation, entropy and [H°(298)-H°(0)]) of key chemical substances.

WABT - Weighted Average Bed Temperature

Definition and examples of calculation of weighted average bed temperature in adiabatic reactors.

Wet Steam - Enthalpy

Wet steam, dryness fraction and enthalpy.

Sponsored Links

Search Engineering ToolBox

Search is the most efficient way to navigate the Engineering ToolBox!

SketchUp Extension - Online 3D modeling!

Add standard and customized parametric components - like flange beams, lumbers, piping, stairs and more - to your Sketchup model with the Engineering ToolBox - SketchUp Extension - enabled for use with the amazing, fun and free SketchUp Make and SketchUp Pro . Add the Engineering ToolBox extension to your SketchUp from the Sketchup Extension Warehouse!

Privacy

We don't collect information from our users. Only emails and answers are saved in our archive. Cookies are only used in the browser to improve user experience.

Some of our calculators and applications let you save application data to your local computer. These applications will - due to browser restrictions - send data between your browser and our server. We don't save this data.

Google use cookies for serving our ads and handling visitor statistics on the AMP pages. Please read Google Privacy & Terms for more information about how you can control adserving and the information collected.

AddThis use cookies for handling links to social media. Please read AddThis Privacy for more information.