Engineering ToolBox - Resources, Tools and Basic Information for Engineering and Design of Technical Applications!

Pressfit Pipes - Supports

Maximum distance between pressfit pipe supports.

Maximum support space for pressfit pipes according

  • ASME B31.1 Power Piping
  • ASME B31.3 Process Piping 
  • ASME B31.9 Building Services Piping
Pressfit Pipes - Supports
NPS
(inches)
DN
(mm)
Support Spacing (feet)
Water ServiceGas or Air Service
B31.1B31.3B31.9B31.1B31.3B31.9
1/2 15 6 6 7 8 8 7
3/4 20 7 7 8 9 9 8
1 25 7 7 9 9 9 9
1 1/4 32 7 7 11 9 9 11
1 1/2 40 7 7 12 9 9 13
2 50 10 10 13 13 13 15
  • 1 ft (foot) = 0.3048 m
3D Engineering ToolBox - draw and model technical applications! 2D Engineering ToolBox - create and share online diagram drawing templates! Engineering ToolBox Apps - mobile online and offline engineering applications!

Unit Converter


















































9.4.10

.
Cookie Settings