Engineering ToolBox - Resources, Tools and Basic Information for Engineering and Design of Technical Applications!

Liquid Ammonia - Thermal Properties at Saturation Pressure

Density, specific heat, thermal conductivity, viscosity and Prandtls no. of liquid ammonia at saturation pressure.

At atmospheric pressure, ammonia, NH3, is present as a liquid at temperatures below -33.6 °C (-28.5 °F). At 10 bara, the condensation/boiling point is 25 °C (77 °F). For more details about phase transitions, see ammonia phase diagram.

Below the tables, properties of liquid ammonia at saturation pressure as function of temperatur, are shown in figures.

Thermal properties of liquid ammonia at saturation pressure :

Liquid Ammonia - Thermal Properties at Saturation Pressure - SI Units
Temperature
- t -
(oC)
Density
- ρ -
(kg/m3)

Specific Heat
(Heat Capacity)
- cp -
(kJ/kgK)

Thermal Conductivity
- λ -
(W/(m K))
Dynamic Viscosity
- η -
( 10-6 Pa s)
Prandtl's no.
-50 698 4.45 0.547 317 1.98
0 636 4.61 0.540 169 1.40
20 609 4.74 0.521 138 1.29
50 561 5.08 0.477 103 1.26
Liquid Ammonia - Thermal Properties at Saturation Pressure - Imperial Units
Temperature
- t -
(oF)
Density
- ρ -
(lb/ft3)

Specific Heat
(Heat Capacity)
- cp -
(Btu/lbmoF)

Thermal Conductivity
- λ -
(Btu/(hr ft oF)
Dynamic Viscosity
- η -
( 10-6 lb/(ft s))
Prandtl's no.
-58 43.4 1.06 0.32 213 1.98
32 39.7 1.10 0.31 113 1.40
68 38 1.13 0.3 93 1.29
122 35 1.21 0.28 69 1.26

Liquid ammonia density saturation pressure C
Ammonia liquid heat capacity Cp C
Liquid ammonia thermal conductivity saturation pressure C Ammonia liquid heat capacity C

Liquid ammonia Prandtl saturation pressure C

3D Engineering ToolBox - draw and model technical applications! 2D Engineering ToolBox - create and share online diagram drawing templates! Engineering ToolBox Apps - mobile online and offline engineering applications!

Unit Converter


















































9.4.10

.
Cookie Settings